IK Ratings

IK ratings are an international classification that indicate the degree of protection provided by electrical enclosures against external mechanical impacts.

IK ratings are defined as IK00 to IK10. The IK rating scale identifies the ability of an enclosure to resist impact energy levels measured in joules (J) in accordance with IEC 62262 (2002).

IEC 62262 specifies how the enclosure must be mounted for testing, the atmospheric conditions required, the quantity and distribution of the test impacts and the impact hammer to be used for each level of IK rating.

Use the table below to find out what the IK rating of our products mean.

IK00 Not protected.
IK01
Protected against 0.14 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 56 mm above impacted surface.
IK02
Protected against 0.2 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 80 mm above impacted surface.
IK03
Protected against 0.35 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 140 mm above impacted surface.
IK04
Protected against 0.5 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 200 mm above impacted surface.
IK05
Protected against 0.7 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 280 mm above impacted surface.
IK06
Protected against 1 joules impact.
Equivalent to impact of 0.25 kg mass dropped from 400 mm above impacted surface.
IK07
Protected against 2 joules impact.
Equivalent to impact of 0.5 kg mass dropped from 400 mm above impacted surface.
IK08

(Walk Over)

Protected against 5 joules impact.
Equivalent to impact of 1.7 kg mass dropped from 300 mm above impacted surface.
IK09
Protected against 10 joules impact.
Equivalent to impact of 5 kg mass dropped from 200 mm above impacted surface.

IK10

(Drive Over)

Protected against 20 joules impact.
Equivalent to impact of 5 kg mass dropped from 400 mm above impacted surface.